Screw air compressor, 75 kW, continuous duty
FST-650L-4T0750G VFD, PLC (S7-200 SMART), output contactor KM1, bypass contactor KM2
After installing a new 75 kW FST-650L VFD on an air-compressor package, the site engineer met sporadic Err03 (over-current) alarms exactly at the moment of frequency-to-mains transfer. Curiously, the trip always happened when the motor current was below the VFD nominal value, indicating a transient spike rather than a true overload.
Physical checks proved no cable or motor insulation fault; the only special item was an output contactor KM1 used to switch the motor terminals between the VFD and the mains contactor KM2.
Root Cause Analysis
The original PLC sequence was:
Send “stop” to VFD (ramp-down mode)
Wait 5 ms
Open KM1, close KM2
Because the motor is highly inductive, the ramp-down phase still delivers current. When KM1 contacts open at non-zero current, the stored magnetic energy forces a high dV/dt across the opening gap, re-striking an arc and injecting a narrow but tall current pulse back into the VFD’s IGBTs. The internal HW circuit of the FST-650L detects this spike as an instantaneous over-current and issues Err03.
Change stop mode from “ramp” to coast-to-stop – output transistors shut off immediately, so current falls to zero within one PWM carrier cycle.
Zero Err03 trips during the first 18 months of operation.
Inductive load switching on the VFD output side is a high-risk action. A coast-to-stop command combined with a zero-current confirmation provides a simple, reliable fix. The FST-650L’s built-in RUN relay is an excellent, low-cost safety interlock—use it before you move the contactor!